Coil side and contact side
Every relay and contactor has two separate ratings, and mixing them up is the commonest ordering mistake.
The coil (control side) is what switches it: typically 24 V DC from a PLC output, or 24, 110 or 230 V AC. The coil voltage is printed on the device and is usually in the type code. A 24 V DC coil on 230 V AC burns out in seconds; a 230 V AC coil on 24 V DC simply does nothing.
The contacts (load side) are what it switches. Their rating depends on the kind of load. IEC 60947 names these as utilization categories: AC-1 for resistive loads such as heaters, AC-3 for starting and stopping squirrel-cage motors, AC-15 for switching other coils, DC-13 for DC coils and valves. A contact good for 10 A of heater current carries much less in AC-3 or DC-13, so check the line in the datasheet that matches your load.
What a relay is for
A relay is a small electromechanical switch, usually rated up to about 6 to 16 A. In a cabinet its main job is coupling: a PLC output drives the coil at 24 V DC, and the contact switches something the PLC output cannot, such as a 230 V AC valve or a different circuit that must stay galvanically separate.
Interface relays sit in sockets on the DIN rail so the relay can be pulled and swapped without touching the wiring. A slim Finder 34 series relay goes in a 6.2 mm Finder 93.51 socket (we have 31); Finder 40 series relays go in a 95.75 socket; Schneider's RXM relays with 2 or 4 changeover contacts go in an RXZE2M114M. When you replace a plugged relay, match the socket's pinout and the coil voltage, and keep the relay series the same.
Relay vs contactor
A contactor works on the same principle, a coil pulling an armature that closes contacts, but it is built for power. It has three (sometimes four) main poles for a three-phase load, arc chutes to break motor current, and room for auxiliary contacts for the control circuit.
| Relay | Contactor | |
|---|---|---|
| Typical use | Signals, small loads, coupling a PLC output | Motors, heaters, three-phase loads |
| Contacts | 1 to 4 changeover | 3 or 4 main poles plus auxiliaries |
| Rated by | Contact current per load type | Motor power in kW at AC-3, and current |
| Mounting | Plug-in socket or PCB | Directly on the DIN rail, screw terminals |
As a working rule, if it is a motor, or more than a few amps on three phases, it wants a contactor.
Motor protection
A contactor switches a motor but does not protect it. The protection is a separate device in front of it:
- A motor protective circuit breaker (Siemens 3RV, Schneider GV2, Eaton PKZM0 type) combines a magnetic short-circuit trip with an adjustable thermal overload trip, set to the motor's nameplate current.
- A thermal overload relay clips under the contactor and opens the coil circuit on overload; short-circuit protection then comes from fuses or a breaker upstream.
Phoenix Contact's ELR hybrid motor starters put all of this in one 22.5 mm housing. The ELR H5 types are reversing starters for three-phase motors with electronic overload protection; we have ELR H5 IES units.
Phase sequence relays like the Crouzet EWS and monitoring relays like the Carlo Gavazzi DUA01 are the other half: they watch the supply and stop a motor from starting backwards or on a missing phase.
Solid state relay (SSR)
A solid state relay switches the load with a semiconductor (a thyristor or triac pair for AC) instead of a contact. Nothing moves, so it does not wear out, does not click, and can switch many times a second.
That makes it the standard choice for heater control. A temperature controller pulses the heater on and off every second or so to hold a setpoint; a mechanical contactor doing that would be worn out within months. An SSR with zero-cross switching turns on only when the AC voltage passes through zero, which keeps the interference low with resistive loads. Random turn-on (non-zero-cross) types are used for inductive loads and phase-angle control.
What you pay for it:
- Heat. An SSR drops a volt or so across its output, so it turns roughly a watt per amp into heat. Above a few amps it needs a heatsink, and the datasheet's current rating is only valid with the specified one.
- Leakage. A small current flows when it is off. A sensitive load, such as another relay coil or a PLC input, may not drop out.
- Failure mode. When an SSR fails, it often fails shorted, leaving the load on. That is why a heater circuit has an independent over-temperature cutout, and why an SSR is never a safety device.
On the shelf: Comat Releco CR11L210 DIN-rail SSRs for heating elements, Celduc SOD86518010 single-phase SSRs, and ten Weidmüller SSR modules.
Timer relay functions
A timer relay is a relay with a delay set on a dial. Two functions cover most needs:
- On-delay: the contact closes a set time after the control signal arrives, and opens immediately when it goes. Used for staggered motor starts or for ignoring short sensor flickers. Star-delta starting has its own dedicated star-delta timers.
- Off-delay: the contact closes at once, and opens a set time after the signal goes away. Used for fans that run on after a heater switches off, or a conveyor that clears before stopping.
Multifunction timers add interval, flasher and pulse functions, chosen by a switch on the front. When you replace one, match the function as well as the time range: an on-delay set to 10 s and an off-delay set to 10 s do opposite things. Check also whether an off-delay type needs permanent supply plus a separate control input, as many do.
Ordering a replacement
Give us the full type code from the label; the coil voltage is usually in it. We hold relays, SSRs, sockets and protection devices from Finder, Phoenix Contact, Schneider, Comat Releco, Weidmüller and others in Szeged, listed under relays and switching. We describe each piece's condition in the quote and ship by FedEx. Ask for a price.